Explosion-proof lights should be checked from the nameplate and product manual before installation: explosion-proof type, category, level, group; protection level of the enclosure; installation method and requirements for installation fasteners, etc.

The installation of the explosion-proof lamp must ensure a firm fixation, the fastening bolts shall not be replaced at will, and the spring washers shall be complete. The dust-proof and waterproof sealing ring should be placed as it is when installing. Where the cable enters, the cable and the sealing gasket should be closely matched, the cross section of the cable should be round, and the surface of the sheath should not have defects such as unevenness. Excess inlets must be sealed according to the explosion-proof type, coated with 201 replacement anti-rust oil, and tighten the compression nut to seal the inlets. For led explosion-proof lights where there is strong vibration, use anti-falling rings to prevent the lights from falling off.